MODULYS XS

The ultimate modularity for the most critical environments - from 2.5 to 20 kVA/kW

Designed with no single point of failure, the MODULYS XS offers high availability and redundant power supply to very critical applications.


With its flexible modularity providing seamless and risk-free power scalability up to 20 kW, the MODULYS XS range is the ideal solution for unscheduled site upgrades or incremental power evolutions. The installed power can be increased up to 20 kW by adding hot-swap plug-in power modules for incremental steps of either 2.5 kW or 5 kW.

Strengths
  • Fully modular system
  • ‘Forever Young’ concept
  • Totally redundant design
  • Enhanced serviceability performance
Conformity to standards
  • IEC 62040-1, IEC 62040-2
  • CE
  • RCM
  • EAC

Advantages

Fully modular system
  • Pluggable and hot-swapped power module with system’s self-setting during installation.
  • All the modules can be swapped without switching to external manual bypass.
  • Hot-swappable battery module designed to be installed with power module in the same UPS enclosure.
‘Forever Young’ concept
  • Eliminates end-of-life criticality.
  • Module compatibility guaranteed for 20+ years.
  • Allows for the implementation of future module technology.
Totally redundant design
  • N+1, N+X redundancy level.
  • Totally independent power modules to avoid any single point of failure.
  • Real selective module disconnection with galvanic separation.
  • Distributed parallel control.
Enhanced serviceability performance
  • Fast & safe maintenance based on hot-swap modules.
  • Designed for concurrent maintenance.

Technical Data

UPS System
Model MC RM
Slot 9 6 4 3
Power [Sn] up to 20kVA up to 15kVA
Power [Pn] up to 20kW up to 15kW
Power factor 1
Number of power modules 4 3
Input/Output X/1
Redundant configuration N+x

 

Input
Model MC RM
Rated voltage 230V 1ph+N (±20%), 400V 3ph+N (±20%)
Frequency 50/60Hz ±10%
Power factor >0.99

 

Output
Model MC RM
Voltage 230V (1ph) ±3% (can be set 208/220/240V)
Frequency 50/60Hz ±2% (±0.1% in battery mode)
Overload 110% for 1 minute, 130% for 10 seconds, 200% for 5 cycles

 

Bypass
Model MC RM
Voltage rated output voltage ±15%
Frequency 50/60Hz ±2% (configurable for GenSet compatibility)

 

Efficiency
Model MC RM
Online double conversion mode up to 92.8%

 

Environment
Model MC RM
Ambient temperature 0 to 40°C (15 to 25°C for maximum battery life)
Relative humidity 0 to 95% without condensation
Maximum altitude 2000m without derating

 

UPS cabinet
Model MC RM
Display 7” touch 3.5”
Dimensions W x D x H (mm) 550 x 635 x 1460 550 x 635 x 1060 449 x 570 x 708 449 x 570 x 575
Weight (empty cabinet) (kg) 120 90 50 44
Colour RAL 7016
Degree of protection IP20

 

Standards
Model MC RM
Safety IEC 62040-1: 2017 (CB Report)
EMC IEC 62040-2: 2005
Product declaration CE, RCM (E2376), UKCA, EAC
Longer back-up time available on demand.

Communication

Standard communication features
  • User-friendly 7-inch touch-screen multilingual colour graphic display (MC models).
  • LCD multi-lingual graphic display (RM & TC models).
  • 2 slots for communication options.
  • USB port to download UPS report and log file.
  • Ethernet port for service purpose.
Communication options
  • Dry-contact interface (configurable voltage-free contacts).
  • MODBUS RTU RS485 or MODBUS TCP.
  • BACnet/IP interface.
  • NET VISION: professional WEB/SNMP Ethernet interface for secure UPS monitoring and remote automatic shutdown.
  • IoT gateway for Socomec cloud services and SoLive UPS mobile app.
  • Remote touch-screen panel.

We’re here to help

Our technical experts are on hand to answer any questions on installation,
commissioning, maintenance, product selection and software updates.