Active Power Filter (APF)

Enersine Modular

Maximum performance and versatility for any load size – from 400 to 600A

Ablerex Active Power Filter (APF) with modular topology from CSPM is the ideal solution to compensate for variable power factor and harmonics. With high current ratings from 400 to 600A it can be adapted to any load size for maximum versatility of use.

Perfect for:

Medical
Industry
Highly polluting loads
CNC machines
Airports
Motor drive systems

Features

  • The scalability of the Modular structure protects your investment over time.
  • The power modules are easy to install and are hot swappable: they can be replaced while the filter is operating.
  • Versatile thanks to the modularity, high nominal current and possibility of parallel connection up to 400 A for the wall version, and up to 2400 A for the modular version.
  • Enersine is available in two versions, 4 or 6 modules for 60 A, 80 A or 100 A, which can also be used in a mixed configuration within the same system.
  • Maximum performance with 3-level DSP technology.
  • Compact, high-power-density design that optimises space.
  • Multi-purpose: one model covers all three-phase systems (3-wire or 4-wire).
  • Correction of all harmonics up to the 51st (up to the 25th for 30 A) with a response time of less than 1 ms.
  • No overload effect.
  • Selective mode allows the selection of harmonics to be corrected.
  • Phase balancing of three-phase loads.
  • Open loop or closed loop installation.
  • A single control module manages up to 8 power modules.
  • All parameters are under control via the 7-inch colour (2.7-inch LCD for 30 A model) touch screen display that shows: voltage and current waveforms, frequency spectrum, parameters and events.
  • Events and parameters can be downloaded to a removable SD card.
  • Advanced communication: dry contacts (3 in and 1 out), USB, RS485 Modbus, RJ45 Ethernet, programmable email alarm.

Technical data

MODEL ENERSINE 400 ENERSINE 600
SIZE (A) 400 600
POWER MODULE (A) 60-80-100
ELECTRICAL SPECIFICATIONS Rated voltage 400 V +15%, -20%; 480V +10%, -20%
Phases Three-phase
Frequency 50/60 ±3 Hz
Harmonic correction From the 2nd to the 51st
Power factor correction Capacitive and inductive (selectable)
Load balancing Between two phases and between phase and neutral
Response time 25 μs
ENVIRONMENTAL PARAMETERS Operating temperature -10°C to +40°C with no derating
Relative humidity <95%
Altitude (a.s.l.) <1000 m with no derating, >1000 m with 1% derating for every 100 m
Audible noise at 1 m. <63 dBA
GENERAL Dimensions (WxDxH) mm 600x900x1500 600x900x1950
Weight (kg)* 150 196
Protection class IP21
Connections 4-wire/3-wire
Installation Floor standing
Type Modular
Parallel connection up to (A) 2400
Max. no. of modules per system (60 or 80 A in a mixed configuration) Up to 4 Up to 6
Max. parallel systems 6 4
TA configuration Source side TA: closed loop control - load side TA: open loop control
CONNECTIVITY Built-in communication ports USB, RS485, Modbus RTU, EPO Ethernet port and dry relay contacts (1 in/3 out)
User interface 7’’ colour LCD touch screen display
Software Data monitoring and storage software
REGULATIONS Standards EN61000-3-4, IEEE 519-1992, EN60146, EN50178; UL508, EN61000-6-4, EN55011, CISPR 11, IEC 61000-3-12, IEC 61000-3-11, IEC 61000-6-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 62477-1, IEC 61000-4-5, IEC 61000-4-6, EN 61000-4-8, EN61000-4-34
Marking CE, UKCA

 